Autronica 116-BDH-300/SPARE Heat Detector with SelfVerify – AutroGuard Retro Variant

The Autronica 116-BDH-300/SPARE replaces the Autronica 116-BDH-300. Autronica provides spare part detectors, specifically intended to replace legacy detectors. Autronica legacy detectors are simply replaced with the spare part detector. The 116-BDH-300/SPARE provides the same functionality/configurability as the Autronica 116-BDH-300 it replaces.

The Autronica 116-BDH-300/SPARE replaces the Autronica 116-BDH-300. Autronica provides spare part detectors, specifically intended to replace legacy detectors. Autronica legacy detectors are simply replaced with the spare part detector. The 116-BDH-300/SPARE provides the same functionality/configurability as the Autronica 116-BDH-300 it replaces.

Please check that the socket installed on board have been produced after 2004, otherwise you need to install the new BWA-100!!

Features
Spare part detector used to replace Autronica legacy detectors 1 to 1
The spare part detector provides the same functionality as the legacy detector it replaces
Easily mounted onto existing AutroSafe/Autroprime bases (BWA-100/BWA-101), no need to replace legacy bases
No software upgrade or re-configuration is necessary
Provides all detection benefits from AutroGuard® protector V-430
Fully compatible with AutroSafe version 3.6 and higher, and all Autroprime versions

AutroGuard RETRO is compatible with:
BBR-130, addressable base sounder
BBQ-130, addressable base sounder/strobe
BBR-52, Smartbuzzer

The Autronica 116-BDH-300 is a point heat detector, and detects a rise in the ambient temperature caused by a fire. The BDH-300 is designed to be used with the Autronica Autrosafe and Autroprime interactive fire alarm systems. The Autronica BDH-300 comes with a SelfVerify function, which ensures the highest grade of reliability. Units with SelfVerify are automatically tested with a calibrated test every 24 hours.

The Autronica BDH-300 is used in areas where false or unwanted alarms are likely, such as:
Galleys
Bathrooms
Kitchens
Boiler Rooms
Workshops

Features
Interactive
Plug-in detector head
Heat detector intended for use in dry areas
Short circuit isolator in each detector
Conforms to EMC directive
Comprises a built-in alarm indicator (LED)
Automatic addressing
Proven technology
Configurable to class A1, A1R, A2S, B, C
The BD-300 is not influenced by dust, humidity, exhaust gases, or electro-magnetic fields, such as radio transmitters, cellular phones, etc.
EN 54-5/EN 54-17
Designed to meet the requirement of the major maritime classification societies

Weight

~140 g

Material

PC/ABS

Color

White

Voltage

10 – 27 VDC

Current Consumption - Stand By

< 0,3 mA

IP Rating

IP44D

Operating temperature

-20 to +80 °C

Humidity

Max. 95%

CPD Certificate

1134-CPD-017